HMI Water Quality and Flow Controller

Frequently Asked Questions

  • A
    1. Product Basics
      Q1: About HMI?
      The HMI is an AQUAS multi-parameter water quality controller used for water quality and flow monitoring, data acquisition, logging, transmission, alarms, and control.

      Q2: What parameters can the HMI monitor?
      The HMI can be used with SMR digital sensors and the MAX multi-parameter analyzer to monitor parameters such as pH, ORP, conductivity, temperature, dissolved oxygen, turbidity, suspended solids, ammonia nitrogen, nitrate nitrogen, flow rate, flow velocity, water level, and water pressure.

      Q3: What applications is the HMI suitable for?
      The HMI is suitable for water treatment, industrial processes, wastewater discharge, drinking water, agriculture, aquaculture, and other sites that require multi-parameter monitoring and control.

      Q4: Can the HMI connect to multiple sensors?
      Yes. The HMI can connect to up to eight SMR sensors via RS485.

      Q5: Does the HMI support the MAX multi-parameter water quality analyzer?
      Yes. The HMI can connect to the MAX multi-parameter water quality analyzer, H2O full-spectrum water quality analyzer, SMR digital sensors, and I/O modules.

      Q6: Can the HMI connect to AQWEB?
      Yes. The HMI can work with the AQWEB cloud management platform for remote display, control, alarm overview, trend charts, data statistical analysis, and reporting.

      Q7: Does the HMI support mobile communications?
      Yes. Depending on the model, the HMI can support communication methods such as GPRS / 4G, WiFi, Ethernet, LoRa, and satellite communication.

      Q8: Does the HMI support Modbus?
      Yes. The HMI supports RS485 Modbus RTU and can also communicate via Modbus TCP/IP over Ethernet.

      Q9: Can the HMI log data?
      Yes. The HMI has built-in data logging. According to the manual, it can store large volumes of data records and supports data upload, alarm logging, and historical queries.

      Q10: Can the HMI be used for alarms and control?
      Yes. The HMI provides alarm limit settings, alarm records, digital output (DO), analog output (AO), PID control, schedule control, and alarm output functions.

      Q11: Does the HMI have a touchscreen?
      Yes. The HMI has a color LCD touchscreen panel that displays real-time values, units, status, alarms, and operation menus.

      Q12: What HMI models are available?
      The manual includes two device architectures: HMI1 and HMI2. HMI1 is a smaller controller, while HMI2 supports more connection ports and expansion functions.

  • B
    1. Installation and Port Questions
      Q1: What are the main ports on HMI1?
      HMI1 includes a system configuration port, Port 1 RS485 sensor port, Port 2 digital I/O port, SIM card slot, and a solar panel or external power port.

      Q2: What are the main ports on HMI2?
      HMI2 includes a system configuration port, Port 0, Port 1 RS485 sensor port, Port 2-1 digital I/O, Port 2-2 analog I/O, AC power port, Ethernet communication port, Modbus TCP/IP Ethernet port, SIM card slot, and power port.

      Q3: What is Port 1 on the HMI used for?
      Port 1 is the RS485 sensor port and can connect up to eight SMR sensors.

      Q4: What is Port 2 on the HMI used for?
      Port 2 is the I/O port and, depending on the model, can support digital input, digital output, analog input, and analog output.

      Q5: What is Port 0 on the HMI used for?
      Port 0 is used for system communication. HMI2 can connect to a PLC or PC through CAB03-E.

      Q6: What should be connected to the HMI system configuration port?
      The system configuration port uses CAB06 to connect to a computer and works with AQCFG software for setup and operation.

      Q7: Does the HMI support a SIM card?
      Yes. The HMI has a SIM card slot. When using mobile communication, remove the protective cover and install the SIM card.

      Q8: Can the HMI use a solar panel?
      Yes. The HMI can connect to an external power source through the solar panel port or CAB01-A.

      Q9: What are the main components on the front of the HMI?
      The front of the HMI includes the touchscreen control panel, alarm light, and 4G / GPRS / WiFi antenna.

      Q10: How do you wake the HMI if it enters sleep mode?
      If the HMI is in sleep mode, press the power / wake button on the side or top.

      Q11: Can the HMI be wall-mounted or pole-mounted?
      Yes. The manual provides wall-mount and pole-mount installation diagrams. The main unit, solar panel, and instrument enclosure can be secured according to site conditions.

      Q12: What cables are commonly used for HMI wiring?
      Common cables include CAB06, CAB03-E, CAB04-A, CAB04-C, CAB01-A, and CAB05-E, used respectively for system setup, PLC / PC connection, I/O connection, power, and Ethernet communication.

  • C
    1. Login and Main Screen Operation
      Q1: How do you power on or wake the HMI?
      Press the wake button to turn on the HMI.

      Q2: What is the password for entering the HMI main display screen?
      According to the manual, after startup, enter password 1111 and press "Confirm" to enter the main display screen.

      Q3: What is the default password for entering operation settings?
      On the main display screen, tap "Operation", then "Password", enter the default password 0000, and press Confirm to begin configuration.

      Q4: What information is shown on the HMI main screen?
      The main screen can display real-time values, units, date and time, location name, battery or status information, alarm prompts, and function menus.

      Q5: What is "Settings" on the main screen used for?
      "Settings" opens function pages such as basic information, location, main screen layout, and I/O settings.

      Q6: What is "Operation" on the main screen used for?
      "Operation" opens function pages such as I/O scanning, recording, and upload.

      Q7: What is "Limits" on the main screen used for?
      "Limits" is used to configure alarm levels and alarm conditions.

      Q8: What is "Alarm" on the main screen used for?
      "Alarm" opens the alarm history page to view past alarm events.

      Q9: What happens when you tap a value on the main screen?
      Tapping any value opens the trend chart page for that value.

      Q10: What does tapping the left title of each display box do?
      Tapping the left title of a display box opens the display settings page, where you can set the device and unit shown in that box.

      Q11: What does tapping the right title of each display box do?
      Tapping the right title of a display box opens the calibration page for that device.

      Q12: What do the H, HH, L, and LL icons mean?
      H and HH indicate high or high-high alarms; L and LL indicate low or low-low alarms.

  • D
    1. Trend Chart and Display Settings
      Q1: How do you view a trend chart?
      Tap any real-time value on the main screen to open the trend chart page for that value.

      Q2: What does 1-1 at the top of the trend chart mean?
      1-1 represents the first unit value in the first sensor window. The first number indicates the sensor number, and the second number indicates the unit number.

      Q3: Can the vertical axis range of the trend chart be adjusted?
      Yes. Tap the Lo limit and Hi limit values, set the desired vertical-axis range, and press Confirm.

      Q4: Can the time range of the trend chart be adjusted?
      Yes. Tap the minute or time options at the bottom to select the horizontal-axis range, such as 5 Min, 15 Min, 30 Min, 1 Hour, 8 Hours, or 24 Hours.

      Q5: How do you return from the trend chart page?
      Tap "Back" or "Exit" to return to the previous page.

      Q6: How do you enter numbers?
      When a number is required, a numeric keypad appears. Enter the number and press ENT.

      Q7: How do you set which device is shown on the home screen?
      Tap the left side of the display title, select the device ID to display, and press "Confirm".

      Q8: How do you set the unit shown on the home screen?
      After entering the display settings page, select the unit to be shown for that channel.

      Q9: Can the numbers on the home screen be made smaller?
      Yes. In display settings, check "Size" to reduce the number display size on the home screen.

      Q10: How do you exit after completing display settings?
      Tap "Back" to complete the settings and return to the previous page.

  • E
    1. Sensor Calibration
      Q1: How do you enter the sensor calibration page?
      Tap the right side of the display title on the main screen, enter the default password 1111, and press ENT to enter the "Calibration" page.

      Q2: Can the HMI directly calibrate SMR sensors?
      Yes. The HMI provides a calibration operation interface for SMR sensors, but the detailed calibration procedure should follow the user manual for each SMR sensor.

      Q3: Which sensor calibration examples are listed in the manual?
      The manual lists calibration screen examples for SMR04 pH, SMR07 conductivity, SMR09 dissolved oxygen, and SMR12 suspended solids.

      Q4: Where should the sensor be placed before calibration?
      Place the SMR sensor in the corresponding standard solution, then press "Calibration".

      Q5: What is the order for zero and slope calibration?
      The manual notes that zero calibration must be completed before slope calibration.

      Q6: What does flashing indicator lights mean during calibration?
      During calibration, two indicator lights flash to show that calibration is in progress. Wait until calibration is complete.

      Q7: What should be noted for SMR09 dissolved oxygen calibration?
      In the SMR09 dissolved oxygen example, zero calibration requires placing the analyzer in a 0% solution, while slope calibration is performed with the analyzer in air.

      Q8: Which manual should be used for calibration details?
      The HMI manual only provides the calibration entry point and screen examples. For each sensor’s standard solution, concentration, procedure, and precautions, refer to the corresponding SMR user manual.

      Q9: How do you confirm calibration after completion?
      Return to the main screen to check the real-time value, or open the trend chart to verify that the reading is stable and matches the standard solution value.

  • F
    1. System Settings and RS485
      Q1: What items can be configured on the system settings page?
      The system settings page allows configuration of Port 0, serial number, station name, latitude, longitude, altitude, the number of main screen displays, RS485, DI, AI, DO, AO, and communication settings.

      Q2: What is the station name used for?
      The station name can be set by the user and can contain up to 20 letters, making it easier for AQWEB to manage and identify the station.

      Q3: How can location information be configured?
      Latitude, longitude, and altitude can be obtained through the GPS module or set manually.

      Q4: How many display panels can be configured on the main screen?
      You can select the number of displays on the home screen, such as 1, 2, 4, 6, or 8.

      Q5: What are the default serial port settings for Port 0?
      The Port 0 serial port is used to scan the RS485 interface. The default settings are 9600 bps, 8 data bits, no parity, and 1 stop bit.

      Q6: How do you save changes to Port 0 parameters?
      After changing the parameters, press the "Update" button to save the correct settings.

      Q7: What can the HMI Ethernet port do?
      Ethernet parameters can be used to poll the HMI Modbus values over TCP/IP.

      Q8: What should be noted when connecting to a PLC / NB via Ethernet?
      The PLC / NB and HMI must be set to the same network segment and access the HMI using the correct Modbus address.

      Q9: What is the default Modbus TCP port for HMI Ethernet?
      The manual states that the default port on the HMI is 8000.

      Q10: How do you scan RS485 sensors?
      After connecting SMR sensors to the HMI, go to the RS485 device page and tap "Scan" to update the RS485 devices.

      Q11: How many RS485 devices can the HMI scan at most?
      The HMI can connect to up to eight RS485 devices.

      Q12: What else should be configured after enabling an RS485 device?
      Check "Enable" to activate the device, check "Interval" to record data, check "Alarm" to enable alarm functions, then press "Confirm" to complete the settings.

      Q13: What restrictions apply to RS485 device IDs?
      Each RS485 device ID must be unique and must be within the range of 1 to 8.

  • G
    1. DI / AI / DO / AO Settings
      Q1: What is DI?
      DI stands for Digital Input and can be used for status input or counter input.

      Q2: What modes does DI provide?
      DI can be set to "Status" or "Counter" mode.

      Q3: What can be configured in DI status mode?
      Status mode can configure periodic logging, alarm logging, alarm levels, and alarm status.

      Q4: What can be configured in DI counter mode?
      Counter mode can configure the value per pulse, unit, accumulated value unit, initial value, automatic reset time, instantaneous value unit, averaging time, and alarm conditions.

      Q5: What is AI?
      AI stands for Analog Input and can receive 4-20 mA analog signals and convert them into engineering values.

      Q6: What information is required when configuring AI?
      Enable analog input, select the 4-20 mA signal, set the unit, minimum value, and maximum value, and optionally check periodic and alarm logging.

      Q7: What is DO?
      DO stands for Digital Output and can be used for manual output, air purge, alarm output, or schedule control.

      Q8: How do you operate DO in manual mode?
      Select digital output 1 or 2, choose manual mode, press ON to output a signal, and press OFF to stop.

      Q9: What is DO air purge mode?
      Air purge mode enables digital output and sets the output duration for air cleaning or related control applications.

      Q10: How do you configure DO alarm mode?
      After enabling DO, select alarm mode, check the I/O device that triggers the DO, select alarm output ON or OFF, and press Confirm.

      Q11: How do you configure DO schedule mode?
      After selecting schedule mode, set the output start and end dates and the ON / OFF times. For example, enter 0915 for 09:15 and 1930 for 19:30.

      Q12: What is AO?
      AO stands for Analog Output and can output a proportional 4-20 mA signal for external control or signal transmission.

      Q13: How do you configure AO manual mode?
      Select analog output 1 or 2, confirm that AO is enabled, select manual mode, and enter the percentage corresponding to the 4-20 mA output ratio.

      Q14: What is AO PID mode?
      PID mode performs automatic control based on process and control parameters so the output gradually approaches the setpoint.

      Q15: How do you configure AO loop output mode?
      Select loop output mode and the process parameter, then set the SMR ID, output percentage, 4 mA lower-limit value, and 20 mA upper-limit value.

  • H
    1. Communication and Data Upload
      Q1: What communication modules does the HMI support?
      Depending on the model, the HMI can support modules such as 4G, GPRS, WiFi, Ethernet, LoRa, NB-IoT, and satellite communication.

      Q2: How do you enter communication settings?
      On the system page, tap "Communication", then select a communication module such as 4G, WiFi, or Ethernet for configuration.

      Q3: What information must be configured for the 4G mobile module?
      Enable the module and enter the SIM card PIN and APN. If the carrier provides a username and password, enter those as well.

      Q4: What must be configured in CCS mode?
      Select CCS mode, enter the server host IP address or URL, and enter the server communication port. The default port is 502.

      Q5: How do you test after configuring 4G / CCS?
      After entering the configuration data, tap "Test" to confirm that the connection is successful.

      Q6: Does the HMI support a backup server?
      Yes. To send HMI data to a second server at the same time, check backup server and enter the IP and port of the second server.

      Q7: Does the HMI support FTP data transmission?
      Yes. The manual includes an FTP data format appendix for data upload and downstream system integration.

      Q8: Can the HMI be remotely monitored through AQWEB?
      Yes. The HMI can connect to the AQWEB cloud management platform for remote monitoring, alarm overview, trend charts, data statistics, and reporting.

      Q9: What should be checked when communication reception is poor?
      The manual recommends keeping the receiving side of the device, the side with the LED indicators, facing upward with no obstruction above it to improve GPS and GSM / GPRS reception quality.

      Q10: Is GPS positioning always accurate?
      Not necessarily. GPS and GSM signal reception and positioning accuracy are affected by installation location and environmental conditions, so good reception cannot be guaranteed in every environment.

  • I
    1. Alarms, Records, and Safety
      Q1: What alarm levels can be configured on the HMI?
      The HMI can configure alarm levels such as high-high, high, low, and low-low, and trigger alarms based on different sensors, DI, AI, or I/O conditions.

      Q2: Does the HMI record alarms?
      Yes. The HMI can record alarm data, and the alarm history page can be accessed from "Alarm" on the main screen.

      Q3: Can the HMI send alarm notifications?
      Yes. Depending on the communication module and settings, the HMI can support alarm notifications, data upload, and alarm display on a remote monitoring platform.

      Q4: Can the HMI use digital output to trigger alarm devices?
      Yes. DO alarm mode can assign an I/O device to trigger digital output for alarm lights, buzzers, or external control.

      Q5: Can the HMI control equipment using a schedule?
      Yes. DO schedule mode can set specific dates and times to turn output on or off.

      Q6: Can the HMI perform PID control?
      Yes. AO supports PID mode and can control output based on process parameters and setpoints.

      Q7: Is HMI operation password-protected?
      Yes. A password is required to enter both the main screen and operation settings. In the manual, the main screen login password is 1111, and the default operation settings password is 0000.

      Q8: What should be noted when using GPS?
      GPS is an optional function and should be used properly to protect privacy. It must not be resold or directly used for unlawful purposes.

      Q9: What are the risks of using non-original batteries or chargers?
      The manual warns that using an incorrect battery type or a non-original charger may create an explosion risk. Used batteries must be handled according to the manufacturer’s instructions.

      Q10: What does the NCC warning remind users of?
      Low-power radio-frequency devices must not have their frequency, power, or original design characteristics changed without authorization, and must not affect aviation safety or interfere with lawful communications.

  • J
    1. Common Troubleshooting
      Q1: What should you do if the HMI cannot be turned on?
      First check whether power is normal and whether external power or solar / battery power is connected. If the HMI is in sleep mode, press the power / wake button.

      Q2: What should you do if you cannot log in to the main screen?
      Confirm that the password is entered correctly. The manual lists 1111 as the password for entering the main display screen.

      Q3: What should you do if you cannot enter operation settings?
      On the main display screen, tap "Operation", then "Password", enter the default password 0000, and press Confirm.

      Q4: What should you do if RS485 sensors cannot be scanned?
      Confirm that the sensor is connected to Port 1, RS485 wiring is correct, the device is powered, the Modbus ID is within the 1 to 8 range, and each device ID is unique.

      Q5: What should you do if an RS485 device is detected but no data is recorded?
      Confirm that the device has "Enable" checked and that "Interval" is checked to record RS485 device data.

      Q6: What should you do if an RS485 device is detected but no alarms occur?
      Confirm that "Alarm" is checked for the device, and configure alarm conditions on the "Limits" page.

      Q7: What should you do if the home screen does not show the correct parameter?
      Tap the left title of the display box and reselect the device ID and unit to be displayed.

      Q8: What should you do if the trend chart does not show an appropriate range?
      Adjust Lo limit and Hi limit, and select an appropriate time range such as 5 minutes, 1 hour, or 24 hours.

      Q9: What should you do if 4G / GPRS communication is poor?
      Check the SIM card, APN, antenna, receiving direction, and obstructions. The manual recommends keeping the receiving side facing upward with no obstruction above it.

      Q10: What should you do if Ethernet Modbus TCP cannot connect?
      Confirm that the HMI and PLC / NB are on the same network segment, the port is set to 8000, and the correct Modbus address is used.

      Q11: What should you do if DO has no output?
      Confirm that DO is enabled, the mode is correct, and the alarm source or schedule is configured. In manual mode, test the output with ON / OFF first.

      Q12: What should you do if AO has no output or incorrect output?
      Confirm that AO is enabled, the mode is correct, and the corresponding 4 mA and 20 mA values are set correctly. In manual mode, enter a percentage to test the output.

      Q13: What should you do if values remain abnormal after calibration?
      Confirm that the correct standard solution was used, the calibration order was correct, and calibration was completed. If the issue remains, refer to the relevant SMR sensor manual or contact AQUAS.

  • K
    1. Recommended Website FAQ Categories
      Q1: How should the website FAQ be categorized?
      Recommended categories include: Product Introduction, HMI1 / HMI2 Differences, Installation and Port Description, Login and Main Screen Operation, Trend Chart and Display Settings, Sensor Calibration, RS485 Sensor Settings, DI / AI Settings, DO / AO Control, 4G / WiFi / Ethernet Communication, AQWEB Cloud Platform, Alarms and Records, Modbus TCP / PLC Integration, Troubleshooting, and Safety and NCC Precautions.