SMR02 Hydrostatic Level Transmitter
Frequently Asked Questions
-
Q1
Product and Basic Use
A- Product and Basic Use
Q1: What is the product?
It is a hydrostatic level meter designed for water level or liquid level monitoring, with digital data output via RS485 communication.
Q2: What is the measurement principle?
It uses the piezoresistive measurement principle. Liquid pressure is transmitted through a stainless steel or titanium alloy diaphragm and an oil-filled isolation structure to a silicon piezoresistive chip. The pressure is then converted into an electronic signal, processed, fully temperature-compensated, and output as liquid level data.
Q3: What application sites is it suitable for?
It is suitable for drinking water, drainage, groundwater, industrial processes, water treatment, wastewater, gas, petrochemical, and other applications.
Q4: Is a control box required?
Not necessarily. SMR02 has an integrated compact enclosure with a built-in transmitter and sensor. It features a rugged IP68 submersible, corrosion-resistant housing and can be installed directly according to site requirements.
Q5: Does it support PLC or HMI?
It uses the standard Modbus RTU communication protocol and can connect to PLCs, HMIs, or AQUAS data loggers via RS485.
Q6: Does it have explosion-proof certification?
Yes. SMR02 is certified with IECEx CoC / ATEX Cat.1, Ex ia IIB T4/T5 Ga/TS explosion-proof certification.
Q7: Is it suitable for outdoor environments without mains power?
Yes. SMR02 features an ultra-low power consumption design and can be used with battery or solar power supply for outdoor or remote monitoring sites.
Q8: Does it have a vent tube?
It uses a vent-tube-free design, preventing damage commonly caused by moisture or water ingress in traditional vent tubes.
- Product and Basic Use
-
Q2
Installation Questions
B- Installation Questions
Q1: What is the operating voltage?
The operating voltage is 5–12 VDC. Use a stable power supply to prevent equipment damage or unstable communication caused by abnormal voltage.
Q2: What installation methods are available?
It is mainly installed by immersion and can be used in water tanks, deep wells, and other liquid level monitoring environments.
Q3: What should be noted during installation?
During installation, avoid pulling or damaging the connection cable. The cable should be long enough and properly secured. It is recommended to install the device at a location with stable water flow to obtain better measurement results.
Q4: What should be noted about the signal cable?
The sensor signal cable should be properly shielded and should not be bundled together with power cables to reduce unstable readings caused by interference.
Q5: Is an exhaust valve required during installation?
If installed in a pipe or vessel where air may be trapped, it is recommended to add an exhaust valve to prevent air from being trapped at the sensing end and causing unstable sensing.
Q6: What should be noted when installing near a pump?
If installed near a pump, it is recommended to add a buffer device to reduce the impact of pressure surges generated when the pump starts or stops.
Q7: Can it be placed directly in bottom sludge?
No. If there is excessive bottom sludge at the installation location, the sensor may be buried or the water inlet may be blocked, resulting in abnormal readings.
Q8: Is there any structural error in water level measurement?
Yes. There is approximately 0.3 cm between the pressure sensing module and the bottom of the device, so the measured water level may differ from the actual water level by approximately 0.3 cm.
Q9: What is the recommended installation method for water tanks?
For water tank installation, the BA05 hanging bracket and a 2-inch protection pipe can be used to secure the sensor at an appropriate depth and prevent shaking, impact, or bottom sludge interference.
Q10: What is the recommended installation method for deep wells?
For deep well installation, the BA05 hanging bracket can be used to secure the cable, lower the sensor to the specified depth, and ensure that the cable is firmly fixed and not pulled.
- Installation Questions
-
Q3
Communication and Wiring Questions
C- Communication and Wiring Questions
Q1: Which communication interface is used?
RS485 communication interface is used.
Q2: Which communication protocol is used?
The standard Modbus RTU communication protocol is used.
Q3: What are the default communication settings?
Common communication settings are as follows:
Communication interface: RS485
Baud rate: 19200 bps
Data length: 8 bit
Parity: None
Stop bit: 1 bit
Communication mode: RTU
The device supports 9600 and 19200 bps.
Q4: Can it be connected directly to a computer?
Yes. It can be connected to a computer using CAB06 USB to RS485 Cable, and values can be read or calibration settings configured through a Modbus tool.
Q5: What is the default device address?
The factory default device address is 01. If the device address is changed, the device address in the PLC, HMI, host, or reading software must also be updated accordingly.
Q6: How should RS485 wiring be connected?
The SMR male connector wiring is as follows:
PIN 1: GND
PIN 2: RS485-
PIN 3: RS485+
PIN 4: 5–12 VDC
PIN 5: Not used
New wire colors are typically: black for GND, white for RS485-, blue for RS485+, and red for 5–12V DC.
Q7: Can it be connected to an AQUAS data logger?
Yes. SMR02 can be connected to AQUAS data loggers such as ECO, HMI1, HMI2, and FLO for data logging and remote monitoring according to site requirements.
Q8: What should be checked first if the PLC cannot read values?
Please check the following in order:
1. Whether CAB06 can be used to connect to a PC and read data via Modbus
2. Whether the communication settings of the PLC and SMR02 are consistent
3. Whether the Modbus ID is correct and whether there is an ID conflict
4. Whether the PLC Modbus address is correct
5. Whether the power supply is stable at 5–12 VDC
6. Whether RS485 wiring is correct
7. Whether the connection has been completed according to the appendix wiring diagram
Q9: What happens if RS485 D+ / D- are reversed?
If RS485+ and RS485- are reversed, the PLC, HMI, or PC may be unable to communicate with the analyzer.
- Communication and Wiring Questions
-
Q4
Modbus Reading Questions
D- Modbus Reading Questions
Q1: Which address should be used to read the main parameter value?
The main parameter value can be read using PLC address 1, HEX address 0x0000, Length 2 Words, Function Code 04, with the data type set to floating point.
Q2: Which address should be used to read the secondary parameter value?
The secondary parameter value can be read using PLC address 2, HEX address 0x0001, Length 2 Words, Function Code 04, with the data type set to floating point.
Q3: How can the temperature value be read?
The temperature value can be read from PLC address 2, HEX address 0x0001, Function Code 04, with the data type set to floating point.
Q4: How can the location, area, or zone name be read?
The location, area, or zone name can be read from PLC address 9, HEX address 0x0008, Length 41 Words, Function Code 03, with the data type set to UTF-16BE string.
Q5: How can the device model be read?
The device model can be read from PLC address 4098, HEX address 0x1001, Length 20 Words, Function Code 04, with the data type set to ASCII string
Q6: How can latitude and longitude be read?
Latitude and longitude can be read from PLC address 10, HEX address 0x0009, Length 6 Words, Function Code 03, with the data type set to floating point.
Q7: How can the cleaning brush be activated?
If the device is equipped with a cleaning brush function, write to PLC address 5, HEX address 0x0004, Function Code 10. The data definition is 0 for standby and 1 for activation.
Q8: How should floating-point data be decoded?
SMR21-2 floating-point data follows the IEEE 754 single-precision floating-point format and occupies 4 Bytes. If the decoded value is abnormal, confirm whether the high/low bytes or word order need to be swapped.
Q9: What should be noted about Modbus CRC?
Modbus RTU uses CRC16. During transmission, Low Byte is sent first and High Byte last, meaning the low-order byte comes before the high-order byte.
Q10: What do Function Codes 03, 04, and 10 represent?
Function Code 03: Read Holding Registers
Function Code 04: Read Input Registers
Function Code 10: Write Multiple Holding Registers
- Modbus Reading Questions
-
Q5
Calibration Questions
E- Calibration Questions
Q1: Is calibration required before initial use?
In general, no. The device has been calibrated before shipment. During initial use, measurement can begin once the device is properly installed according to the manual.
Q2: When is recalibration required?
Recalibration is recommended when on-site water level readings differ significantly from actual measured values, after reinstallation, after installation depth changes, when accuracy needs to be confirmed after maintenance, or when long-term data shows drift.
Q3: What calibration methods are available?
Calibration mainly includes zero-point calibration and slope calibration. Temperature correction can also be performed if required.
Q4: What tools are required for calibration?
The following tools are required:
SMR02 hydrostatic level meter
5–12 VDC stable external power supply
USB to RS485 converter, CAB06 recommended
Personal computer
Q5: Are standard solutions or chemicals required for calibration?
No. No chemicals are required for SMR02 calibration.
Q6: How is zero-point calibration performed?
Place the device in air, read the current zero-point calibration value to confirm its status, then write 1 to the zero-point calibration value to perform calibration. Finally, read the water level value to confirm whether calibration has been completed.
Q7: Which address should the zero-point calibration value be written to?
The zero-point calibration value can be written to PLC address 516, HEX address 0x0203, Function Code 10, with the data type set to floating point.
Q8: How is slope calibration performed?
Place the sensor in the liquid to be measured, enter the correct sensor liquid level into the slope calibration value, and then read the water level value to confirm whether calibration was successful. After calibration, the sensor depth can be adjusted to check whether the liquid level reading is correct.
Q9: Which address should the slope calibration value be written to?
The slope calibration value can be written to PLC address 517, HEX address 0x0204, Function Code 10, with the data type set to floating point.
Q10: Which address should the temperature correction value be written to?
The temperature correction value can be written to PLC address 12289, HEX address 0x3000, Function Code 10, with the data type set to floating point.
Q11: Why should the device be placed in air during zero-point calibration?
Zero-point calibration requires the sensor to be under no liquid pressure, which serves as the water level zero reference. If there is still water pressure or residual liquid at the sensing end, zero-point drift may occur.
Q12: What should be noted during slope calibration?
The correct actual liquid level value must be entered, and the sensor depth must be consistent with the on-site measurement reference. After calibration, change the sensor depth or compare the reading with an on-site staff gauge to confirm whether the reading is correct.
- Calibration Questions
-
Q7
Abnormal Readings and Troubleshooting
F- Abnormal Readings and Troubleshooting
Q1: What should I do if readings keep fluctuating?
First clean the sensing area, check whether the water inlet is blocked, whether air bubbles remain, whether the installation is secure, whether the on-site water flow is excessively disturbed, and whether the signal cable is affected by interference from power cables.
Q2: What should I do if the response time becomes slower?
This may be caused by a blocked sensing water inlet, contamination in the sensing area, bottom sludge attachment, residual air bubbles, or trapped air in the pipeline. It is recommended to clean the sensing end and install an exhaust valve and drain valve if necessary.
Q3: What should I do if the reading does not change?
Restore factory settings first and repeat the calibration procedure. If there is still no response, check the power supply, RS485 communication, wiring, and whether the sensor is damaged, then contact AQUAS technical support.
Q4: What should I do if readings are clearly too high or too low?
Confirm whether zero-point calibration and slope calibration are correct, whether the sensor is installed at the correct depth, and whether bottom sludge burial, residual air bubbles, water inlet blockage, or pump pressure surges are affecting the reading.
Q5: Do air bubbles in the installation environment affect readings?
Yes. Air bubbles may be trapped at the sensing end, causing unstable sensing or reading deviation. It is recommended to add an exhaust valve and confirm that air does not easily accumulate at the installation location.
Q6: What problems can a blocked water inlet cause?
A blocked water inlet may prevent hydraulic pressure from being correctly transmitted to the sensing diaphragm, resulting in abnormal readings, unstable readings, slower response, or no change in readings.
Q7: Does burial by bottom sludge affect readings?
Yes. Bottom sludge may block the sensing area or create additional pressure influence, causing reading deviation or slower response.
Q8: Can pump startup and shutdown affect SMR02?
Possibly. Pressure surges generated when a pump starts or stops may affect sensor readings. It is recommended to install a buffer device near the pump to reduce the impact.
Q9: If on-site readings differ from actual staff gauge readings, does that mean the device is faulty?
Not necessarily. This may be related to the installation reference, sensing position, zero-point or slope settings, 0.3 cm structural error, on-site water flow disturbance, air bubbles, or bottom sludge. It is recommended to first confirm installation and calibration conditions before determining whether maintenance is required.
Q10: When should AQUAS technical support be contacted?
If the device still cannot read values or shows no response after checking power supply, wiring, Modbus ID, communication settings, zero-point calibration, slope calibration, cleaning, and installation, it is recommended to contact AQUAS technical support and provide on-site photos, wiring photos, Modbus settings, calibration records, and reading screenshots.
- Abnormal Readings and Troubleshooting
-
Q8
Maintenance Questions
F- Maintenance Questions
Q1: Is regular maintenance required?
Yes. To keep the level meter in optimal operating condition, regular maintenance and cleaning are required, especially in environments where oil, sediment, or other contaminants may adhere to the device.
Q2: How often should routine maintenance be performed?
Routine maintenance is recommended at least once per week. The actual frequency can be adjusted according to on-site water quality, bottom sludge, oil and grease, and the monitoring environment.
Q3: What should be included in routine maintenance?
Routine maintenance should include:
Cleaning the analyzer surface and sensing area
Checking the battery level, if using a battery-powered model
Checking consumable status
Checking whether cables and mounting fixtures are secure
Confirming whether data transmission is stable
Q4: How often should periodic maintenance be performed?
Periodic maintenance is recommended at least once per month.
Q5: What is included in periodic maintenance?
Periodic maintenance may include trend calibration and long-term data comparison. If necessary, adjust the instrument status according to data trends to ensure stable and accurate measurement results.
Q6: What should be noted when cleaning SMR02?
It is recommended to clean the analyzer surface and sensing area with a soft cloth or a dedicated neutral cleaner. Avoid using hard objects that may scratch the diaphragm or damage the sensing end.
Q7: Are there consumables that need to be replaced regularly?
No specific chemical consumables are listed for the device itself, but the battery, cables, mounting fixtures, and sensing end condition should still be checked regularly. For battery-powered devices, replace the battery according to the battery level status.
- Maintenance Questions