SMR61 Radar Level Meter
Radar Level Meter
- Q1
Product and Basic Use
A- Product and Basic Use
Q1: What application sites is the SMR61 radar level meter suitable for?
The radar level meter is suitable for level monitoring applications such as drainage, surface water, wastewater, reservoirs, rivers, tap water, and sewage.
Q2: What is the measurement principle of SMR61?
It uses FMCW continuous radar wave transmission. The water level is calculated by measuring the time difference of the radar wave reflected back from the water surface.
Q3: Is a control box required?
It has an integrated compact enclosure with a built-in transmitter and sensor, and features an IP68 dustproof and waterproof housing. In some applications, it can be installed and used directly without a control box.
Q4: Does it support PLC or SCADA systems?
Yes. SMR61 uses the standard Modbus RTU communication protocol and can connect to PLCs, HMIs, or SCADA systems via RS485.
- Product and Basic Use
- Q2
Installation Questions
B- Installation Questions
Q1: What should be noted during installation?
During installation, confirm that the sensor is installed vertically downward and aligned with the water surface. Avoid tilting or shaking. The connection cable should be long enough and properly secured to prevent pulling damage.
Q2: What is the operating voltage?
The operating voltage is 5–12 VDC. Use a stable power supply to prevent equipment damage or unstable communication caused by abnormal voltage.
Q3: What is installation height H?
Installation height H refers to the vertical distance from the radar probe to the bottom of the measurement channel or reference surface. This parameter affects the water level calculation result.
Q4: How is the water level converted from the radar-measured distance?
The actual water level L is calculated as: L = H − M, where H is the installation height and M is the radar-measured distance.
Q5: What happens if installation height H is set incorrectly?
If the H value is entered incorrectly, the water level reading may remain consistently too high or too low even after calibration.
Q6: Is there a blind zone?
Yes. The blind zone is approximately 4 cm in front of the radar probe. If the water surface falls within the blind zone, the signal may become unstable or readings may be abnormal.
Q7: Can it be installed at an angle?
It is not recommended. The sensor should be installed vertically and aligned with the water surface. Tilting or offset installation may cause radar reflection deviation and inaccurate measurement.
- Installation Questions
- Q3
Communication and Wiring Questions
C- Communication and Wiring Questions
Q1: Which communication interface is used?
It uses the RS485 communication interface and supports the Modbus RTU communication protocol.
Q2: What are the default communication settings?
Common communication settings are as follows:
Communication interface: RS485
Baud rate: 19200 bps
Data length: 8 bit
Parity: None
Stop bit: 1 bit
Communication mode: RTU
The device supports 9600 and 19200 bps.
Q3: What is the default device address?
The factory default device address is 01. If the device address is changed, the address on the PLC or host side must also be updated accordingly.
Q4: How should RS485 wiring be connected?
The SMR male connector wiring is as follows:
PIN 1: GND
PIN 2: RS485-
PIN 3: RS485+
PIN 4: 5–12 VDC
PIN 5: Not used
New wire colors are typically: black for GND, white for RS485-, blue for RS485+, and red for 5–12 VDC.
Q5: What should be checked first if the PLC cannot read SMR61 values?
Please check the following in order:
1. Whether the Modbus communication settings are consistent
2. Whether the device ID is correct and whether there is an ID conflict
3. Whether the PLC Modbus address is correct
4. Whether the power supply is stable at 5–12 VDC
5. Whether RS485 wiring is correct
6. Whether CAB06 can be used to connect to a computer for testing first
Q6: Why can the computer read the device, but the PLC cannot?
Common causes include different PLC communication parameters, incorrect Modbus address settings, incorrect function code usage, mismatched register start addresses, or reversed RS485 D+ / D- wiring.
- Communication and Wiring Questions
- Q4
Modbus Reading Questions
D- Modbus Reading Questions
Q1: Which address should be used to read the main parameter value?
The main parameter value can be read using PLC address 1, HEX address 0x0000, Length 2 Words, Function Code 04, with the data type set to floating point.
Q2: Which address should be used to read the secondary parameter value?
The secondary parameter value can be read using PLC address 2, HEX address 0x0001, Length 2 Words, Function Code 04, with the data type set to floating point.
Q3: How can the device model be read?
The device model can be read from PLC address 4098, HEX address 0x1001, Length 20 Words, Function Code 04, with the data type set to ASCII string
Q4: How should floating-point data be decoded?
Floating-point data follows the IEEE 754 single-precision floating-point format and occupies 4 Bytes. If the reading is abnormal, confirm whether the high/low bytes or word order need to be swapped before decoding.
Q5: What should be noted about Modbus CRC?
Modbus RTU uses CRC16. During transmission, Low Byte is sent first and High Byte last, meaning the low-order byte comes before the high-order byte.
- Modbus Reading Questions
- Q5
Calibration Questions
E- Calibration Questions
Q1: Is calibration required before initial use?
In general, no. The device has been calibrated before shipment. During initial use, measurement can begin once the device is properly installed according to the manual.
Q2: When is recalibration required?
Recalibration is recommended when the on-site water level differs significantly from the system display value, after reinstallation, after installation height changes, when readings drift over time, or when accuracy needs to be verified after maintenance.
Q3: What tools should be prepared before calibration?
Prepare the following before calibration:
SMR61 radar level meter
Stable external power supply, 5–12 VDC
USB to RS485 converter, CAB06 recommended
Personal computer
Q4: How should installation height H be set?
First measure the vertical distance from the radar probe to the channel bottom or reference surface, then write this value into the installation height H parameter. After writing, read it again to confirm that the setting was successful.
Q5: How is radar water level measurement M calibrated?
First confirm that the analyzer is vertically fixed and that the water level is stable. Wait 30 seconds to 1 minute, then read the radar water level measurement value. If it differs from the on-site measured value, enter a correction value based on the on-site measurement and read again for confirmation.
Q6: Does the pressure-type water level module require calibration?
If the device includes a pressure-type water level module, zero-point calibration is recommended. During calibration, first confirm that installation height H has been correctly set, then perform hydrostatic level correction according to the manual procedure.
Q7: Does the device need to be restarted after calibration?
No. Offset correction is applied immediately, and the device does not need to be restarted.
- Calibration Questions
- Q7
Abnormal Readings and Troubleshooting
F- Abnormal Readings and Troubleshooting
Q1: What should I do if readings keep fluctuating?
Check whether the power supply is stable, whether the device is installed vertically, whether there is foam or turbulence on the water surface, whether floating objects or obstacles are present within the field of view, and whether strong electromagnetic interference exists on site.
Q2: What should I do if the reading remains at 0?
First confirm whether there is a valid water level on site, then check the power supply, communication, installation angle, and blind-zone issues. You can also point the device vertically toward the ground or a wall to test whether it can display a stable distance value. If there is still no response, the module may be abnormal. Please contact AQUAS technical support.
Q3: What should I do if readings are clearly too high or too low?
Confirm whether installation height H is correct, whether the device is installed vertically, whether the water surface is within the blind zone, and whether there are obstacles or reflection interference within the radar field of view. Recalibrate if necessary.
Q4: What should I do if the water level reading responds slowly?
Check whether communication is stable, whether the power supply is normal, whether there is significant interference on the water surface, and whether the system reading cycle and data update settings are correct.
Q5: What are the most common causes of abnormal water level readings?
Common causes include:
Incorrect installation height H setting
Water surface entering the blind zone
Device not installed vertically
Interference from foam, floating objects, or turbulence on the water surface
Reflection interference caused by environmental obstacles
Abnormal RS485 communication or power supply
Q6: When should AQUAS technical support be contacted?
If values still cannot be read after checking power supply, wiring, communication settings, installation conditions, and recalibration, or if data still cannot be read via Modbus after connecting the device to a computer, please contact AQUAS technical support. It is recommended to provide screenshots, on-site photos, wiring photos, and test records.
- Abnormal Readings and Troubleshooting
- Q8
Maintenance Questions
F- Maintenance Questions
Q1: Is regular maintenance required?
Yes. To ensure stable long-term measurement, regular cleaning and inspection are recommended according to the on-site environment.
Q2: How often should routine maintenance be performed?
Routine maintenance is recommended at least once per week. The actual frequency can be adjusted according to on-site water quality, oil and grease, sediment, or contamination level.
Q3: What should be included in routine maintenance?
Routine maintenance should include:
Cleaning the sensor surface
Checking the battery level, if using a battery-powered model
Checking consumable status
Checking whether cables and mounting fixtures are loose or damaged
Q4: How often should periodic maintenance be performed?
Periodic maintenance is recommended at least once per month, and long-term data trends should be used to determine whether trend calibration is required.
Q5: Does contamination on the sensor surface affect readings?
Yes. Oil, grease, sediment, or other contaminants attached to the sensor surface may affect radar signals and measurement accuracy, so regular cleaning is recommended.
- Maintenance Questions