FLO Open Channel Flow Logger
Frequently Asked Questions
-
Q1
General Product Questions
A- General Product Questions
Q1: About product?
FLO is an AQUAS open-channel flow and water-level logger designed for remote measurement, data collection, recording, transmission, alarm notification, and control. It is suitable for flow and water-level monitoring applications in open channels, sewers, rivers, irrigation channels, and similar environments.
Q2: What data can it mainly measure?
By integrating different flow modules and sensors, FLO can measure water level, velocity, instantaneous flow, and accumulated flow. It can also integrate data such as water quality, gas, pressure, digital input, and analog input.
Q3: What application sites is it suitable for?
FLO is suitable for sewer systems, stormwater runoff, municipal and industrial wastewater, rivers and streams, irrigation channels, and other monitoring sites.
Q4: Does it require an external power supply?
Not necessarily. FLO can be powered by an internal battery, external battery, or solar power. Some applications do not require external mains power, making it suitable for outdoor or off-grid sites.
Q5: What is the waterproof and dustproof rating?
FLO features a rugged IP68 enclosure, making it suitable for wet, rainy, flooded, and outdoor environments.
Q6: Does it support RS485 sensors?
Yes. FLO can connect to SMR series digital analyzers, radar level meters, radar velocity and level meters, and other devices via RS485.
Q7: Does it support 4G communication?
Yes. FLO can be configured with 4G/GPRS, Wi-Fi, Ethernet, NB-IoT, and other communication options. Data can be uploaded to AQWEB or other servers.
Q8: Which communication protocols are supported?
FLO supports Modbus RTU, and depending on the communication module, it may also support Modbus TCP or other data upload methods.
- General Product Questions
-
Q2
Installation and Hardware Questions
A- Installation and Hardware Questions
Q1: What should be noted when installing a SIM card?
When using the 4G communication module, a micro SIM card must be installed. Open the upper housing, insert the SIM card into the SIM card slot, then close the cover and tighten it securely.
Q2: Are there any requirements for the 4G antenna installation direction?
Yes. To ensure 4G signal quality, the receiving side of the device, which is the side with the LED indicators, should face upward, and there should be no obstructions above it.
Q3: What external connectors are available?
FLO external ports include:
Port 0: System configuration port, using CAB06
Port 1: Two RS485 sensor connection ports
Port 2: I/O Module
Port 3: Barometric pressure module
Power port: CAB01-A
4G antenna port
Charging indicator
Q4: How do I connect FLO to a computer?
Use CAB06 to connect the computer USB port to FLO Port 0, then use AQCFG software to search for and configure the device.
Q5: How do I connect radar or digital sensors?
Radar or digital sensors are typically connected to FLO Port 1 via RS485, then scanned and enabled on the RS485 page in AQCFG.
Q6: Can it be installed directly in sewers or outdoor environments?
Yes. FLO is designed for outdoor monitoring applications and features an IP68 enclosure. It can be used in sewers, rivers, channels, and similar environments. However, antenna signal quality, secure installation, cable strain prevention, and connector sealing should still be properly checked./span>
- Installation and Hardware Questions
-
Q3
AQCFG Connection and Configuration Questions
B- AQCFG Connection and Configuration Questions
Q1: What must be installed before using AQCFG?
AQCFG software and the USB Driver must be installed first. After installing the USB Driver and connecting CAB06 to the computer, a USB Serial Port should appear in Device Manager.
Q2: What are the default communication settings for connecting to AQCFG?
Common FLO host connection settings are:
Baud rate: 115200 bps
Data Bits: 8
Parity: None
Stop Bit: 1
Modbus ID: 1
Q3: What should I do if AQCFG cannot scan the FLO host?
Please check the following in order:
1. Whether CAB06 is connected to Port 0
2. Whether the USB Driver has been installed successfully
3. Whether the USB Serial Port appears on the computer
4. Whether the correct COM Port is selected
5. Whether the baud rate is set to 115200
6. Whether the Modbus ID search range includes the host ID
7. Whether FLO is powered on or whether the battery voltage is normal
Q4: What is the initial AQCFG password?
When entering the FLO configuration page, the initial password is 0000.
Q5: What do the AQCFG communication status colors indicate?
Green indicates connected, and red indicates disconnected.
Q6: Which button must be clicked to apply the settings after configuration?
After completing the configuration in AQCFG, click “Confirm” to update the settings.
Q7: What should be done before system configuration?
After entering the system page, click “System On” to start the host operation.
- AQCFG Connection and Configuration Questions
-
Q4
System Time and Battery Configuration Questions
C- System Time and Battery Configuration Questions
Q1: How is the FLO system time synchronized?
In general, no manual operation is required. MAX has been calibrated before shipment. During initial use, measurement can begin once the device is properly installed according to the manual and the electrode protective cap is removed.
Q2: Why is the system time important?
System time affects data recording time, alarm time, data upload time, and historical data queries. Therefore, the correct time should be verified during on-site configuration.
Q3: What should be done after replacing the battery?
After replacing the battery, select the correct battery type on the AQCFG system page and click “Reset” or “Zero” so the system can recalculate the battery capacity.
Q4: At what battery voltage should maintenance be performed?
The manual recommends replacing the battery if the battery voltage is lower than 3.4V.
Q5: How often should the FLO battery be inspected?
It is recommended to check the battery voltage and capacity at least once per month. The actual inspection frequency may be adjusted based on the site upload frequency, communication power consumption, and power supply method.
- System Time and Battery Configuration Questions
-
Q5
FLO2 / FLO3 Quick Configuration Questions
D- FLO2 / FLO3 Quick Configuration Questions
Q1: What are the key steps for quick on-site configuration of FLO2?
Key FLO2 configuration steps include:
1. Connect to AQCFG and start the system
2. Select the SMR61 page with ID8
3. Set the radar level meter installation height
4. Set the flow model parameters
5. Confirm water level, instantaneous flow, and accumulated flow
6. Set the recording and upload frequency
7. Perform a 4G Link Test
8. Confirm that new records are available on the LOG page
9. After closing the manhole cover, confirm communication quality in AQWEB
Q2: What are the key steps for quick on-site configuration of FLO3?
Key FLO3 configuration steps include:
1. Connect the SMR63 Sensor first
2. Set the flow direction according to the on-site installation direction
3. Set the radar water-level installation height
4. Connect the FLO3 host and start the system
5. Confirm battery type, battery voltage, and time synchronization
6. Set water level, velocity, and model parameters
7. Confirm instantaneous flow and accumulated flow
8. Set the recording and upload frequency
9. Perform a 4G Link Test
10. Confirm communication quality in AQWEB
Q3: How should the FLO3 flow direction setting be determined?
Set the flow direction according to the on-site installation direction of the velocity meter. If measuring toward the upstream direction, set the reverse velocity reading as positive. If measuring toward the downstream direction, set the forward velocity reading as negative.
Q4: Why is it necessary to confirm that accumulated flow is increasing?
Accumulated flow is added according to the recording frequency. If the accumulated value does not increase, it may indicate an issue with the flow model, recording interval, sensor readings, or system startup status.
- FLO2 / FLO3 Quick Configuration Questions
-
Q6
Flow Model and Sensor Questions
F- Flow Model and Sensor Questions
Q1: Which flow modules can FLO be used with?
FLO can be used with various flow modules, including:
FLO1: Hydrostatic level module
FLO2: Radar level module
FLO3: Radar velocity and level module
FLO4: Doppler velocity and level module
FLO5: Ultrasonic level module
Q2: Which measurement sections or flow models are supported?
FLO supports various open-channel and pipe-channel models, such as weirs, flumes, circular pipes, rectangular channels, U-shaped channels, trapezoidal channels, and river models. During configuration, the correct model must be selected according to the on-site cross section, and the relevant parameters must be entered.
Q3: What happens if the flow model parameters are set incorrectly?
If the pipe diameter, Lmax, slope, roughness, correction factor, or cross-section parameters are set incorrectly, the instantaneous flow and accumulated flow calculations may become inaccurate.
Q4: What should be noted after replacing a sensor?
After replacing a sensor connected to the host, confirm that the Modbus ID of the new sensor does not conflict with the level meter or other devices. Then scan and enable the sensor on the RS485 page in AQCFG.
Q5: What should I do if the sensor cannot be found?
Please check:
1. Whether the sensor is connected to host Port 1
2. Whether the sensor cable and connector are functioning properly
3. Whether the RS485 wiring is correct
4. Whether scanning has been performed on the RS485 page
5. Whether the sensor ID is within the search range
6. Whether there is an ID conflict with other devices
Q6: What should I do if sensor readings are unstable or inaccurate?
Perform calibration according to the sensor type, such as zero-point calibration or slope calibration. Also check the installation height, flow direction, measurement cross section, and on-site flow conditions.
- Flow Model and Sensor Questions
-
Q7
Data Recording and Upload Questions
F- Data Recording and Upload Questions
Q1: What data intervals can be configured?
Alarm sampling interval, periodic recording interval, event recording interval during alarms, and data upload interval can be configured.
Q2: How can data upload be configured?
Data upload can be configured by schedule or fixed interval. In scheduled mode, data is uploaded at selected time points. In fixed-interval mode, data is uploaded to the server based on the configured interval, starting from 00:00 each day.
Q3: What is immediate alarm upload?
When an alarm record occurs, the host immediately starts communication and uploads the data to the server.
Q4: What is alarm-period record upload?
From the start of an alarm until the alarm ends, the system starts a 4G connection and uploads data to the server each time a record is generated.
Q5: How can I confirm that FLO is recording data properly?
You can check whether new records are available on the LOG page or the “Import/Export” page in AQCFG. You can also verify whether uploaded data is complete through data reports or historical data in AQWEB.
Q6: How can I confirm successful upload to AQWEB?
Perform a Link Test on the 4G page in AQCFG, then log in to AQWEB. Search for the device in the left-side device tree and confirm that real-time data, historical data, and trend charts are updated.
- Data Recording and Upload Questions
-
Q8
4G / AQWEB Communication Questions
F- 4G / AQWEB Communication Questions
Q1: What should be checked first when FLO 4G communication fails?
Please check the following in order:
1. Whether the battery voltage and capacity are sufficient
2. Whether the SIM card has been activated and the service fee has been paid
3. Whether the host has been set to “System On”
4. Whether the 4G function has been enabled
5. Whether the APN is correct
6. Whether the antenna is functioning properly
7. Whether the on-site signal quality is good
8. Whether Link Test can be performed
9. Whether log files are stuck and need to be cleared
Q2: Does 4G communication affect the battery?
Yes. 4G communication consumes more power and may cause a voltage drop during communication. Therefore, if 4G upload fails, both the battery status and communication settings should be checked.
Q3: What issues can an incorrect APN setting cause?
An incorrect APN may prevent 4G connection or data upload. If unsure, confirm the APN with the SIM card carrier or try leaving the setting blank as recommended in the manual.
Q4: Why is AQWEB communication quality checked again after closing the manhole cover?
Manhole covers, pipelines, and underground environments may affect 4G signal quality. During on-site testing, the return time and signal quality should be confirmed in AQWEB after the manhole cover is closed, to avoid discovering poor communication only after installation is complete.
Q5: What should I do if AQWEB does not show any data?
Please confirm:
1. Whether the AQCFG Link Test is successful
2. Whether the server IP and Port are correct
3. Whether the SIM card and APN are normal
4. Whether the data upload interval has been configured
5. Whether new data is available on the LOG page
6. Whether the correct device is selected in the AQWEB left-side device tree
7. Whether the device time is correct
8. Whether the 4G signal is sufficient
- 4G / AQWEB Communication Questions
-
Q9
Alarm Configuration Questions
F- Alarm Configuration Questions
Q1: What alarms can be configured?
System alarms, Port 1 digital sensor alarms, Port 2 digital and analog input alarms, barometric pressure alarms, and other alarm types can be configured.
Q2: What items are included in system alarms?
System alarms may include low voltage, communication abnormality, GPS displacement, GPS failure, and other items.
Q3: What alarm levels are available for sensors?
Sensor values can be configured with four alarm levels: HH, H, L, and LL. Corresponding values and alarm messages can also be configured.
Q4: Can alarm SMS messages be sent?
Yes. When used with the 4G communication module and SMS configuration function, custom alarm messages can be sent to designated mobile phone numbers.
- Alarm Configuration Questions
-
Q10
Maintenance and Troubleshooting
F- Maintenance and Troubleshooting
Q1: How often is maintenance required?
It is recommended to perform maintenance at least once per month, including sensor calibration, connection inspection, battery status verification, communication testing, and data upload confirmation.
Q2: What items should be checked during maintenance?
It is recommended to check:
Battery voltage and capacity
Sensor readings
Sensor cables and connectors
RS485 communication
4G communication and antenna
Whether LOG is recording properly
Whether AQWEB upload is functioning properly
Whether alarm settings are functioning properly
Q3: What should I do if there is no power?
Replace or charge the battery first, then confirm whether the battery type setting is correct. If there is still no power or the capacity value remains abnormal, check the battery cable, power cable, connectors, solar panel, or backup battery status.
Q4: What should I do if Port 0 cannot connect?
Confirm whether CAB06 is functioning properly, whether it is connected to Port 0, whether the COM Port is correct, and whether the Modbus ID is correct. Replace CAB06 for testing if necessary.
Q5: What should I do if data is recorded but cannot be uploaded?
Check whether 4G is enabled, whether the SIM card and APN are normal, whether the server IP/Port is correct, whether Link Test is successful, and whether the data upload interval has been configured.
Q6: What should I do if data is not being recorded?
Confirm whether the system has been started, whether the recording interval has been configured, whether the sensor is enabled, whether real-time data has readings, and whether new data is available on the LOG page.
Q7: Does an inaccurate reading always mean the host is faulty?
Not necessarily. Common causes of inaccurate readings include uncalibrated sensors, incorrect installation height, incorrect flow model parameters, incorrect sensor installation direction, unstable on-site flow conditions, or abnormal communication readings.
Q8: When should AQUAS technical support be contacted?
If the system still cannot operate normally after checking power, wiring, COM Port, Modbus ID, sensor scanning, 4G Link Test, SIM/APN, and AQWEB query results, it is recommended to provide on-site photos, wiring photos, AQCFG screenshots, AQWEB screenshots, and LOG data when contacting AQUAS technical support.
- Maintenance and Troubleshooting